8 Technical data
18/02/2021
bplogic intelligent pump controller
275
8.3.3 I/O module 2
I/O module 2 connections
Specification
Value
Unit
Maximum total current for the supply to the digi-
tal outputs
1 A
Maximum total current for the supply to the digi-
tal inputs, analog inputs and analog outputs
1 A
Number of digital inputs
2
Number of digital outputs
4
Number of analog inputs
2
Number of analog outputs
1
Connection: M12 socket (A-coded)
Housing material: Die-cast aluminium
Digital input and output for I/O module 2
Specification
Value
Unit
Digital input signal shape
1)
24 VDC
Digital input filter time
1 ms
Digital output signal shape
2)
24 VDC
Maximum output current
3)
2 A
Electrical isolation
500 V
1)
PNP-reading in accordance with EN 61131-2, type 3 in 3 conductor connection
method
2)
PNP-switching, short-circuit proof in 3 conductor connection method