8 Technical data
18/02/2021
bplogic intelligent pump controller
273
8.3.2 I/O module 1
I/O module 1 connections
Specification
Value
Unit
Maximum total current
1)
1 A
Number of digital inputs
5 + 4
2)
Number of digital outputs
3)
4
Number of analog inputs
1
Number of analog outputs
1
1)
Total current for all supply and signal currents for digital inputs and outputs, and
analog inputs and outputs.
2)
5 Digital inputs and 4 digital outputs that can be configured as inputs
3)
switchable
Connection: M12 socket (A-coded)
Housing material: Die-cast aluminium
Digital input and output for I/O module 1
Specification
Value
Unit
Digital input signal shape
1)
0/24 VDC
Digital input filter time
1 ms
Digital output signal shape
2)
0/24 VDC
Max. current per digital output
3)
0.4 A
1)
PNP-reading in accordance with EN 61131-2, type 3
2)
PNP-switching
3)
from the sensor supply per output, short-circuit proof