5.3.4
Settings
Table 18:
LEDGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
tRestart
0.0 - 100.0
s
0.1
0.0
Defines the disturbance length
tMax
0.0 - 100.0
s
0.1
0.0
Maximum time for the definition of a
disturbance
Table 19:
GRP1_LED1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SequenceType
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
-
-
Follow-S
Sequence type for LED 1, local HMI alarm
group 1
LabelOff
0 - 18
-
1
G1L01_OFF
Label string shown when LED 1, alarm
group 1 is off
LabelRed
0 - 18
-
1
G1L01_RED
Label string shown when LED 1, alarm
group 1 is red
LabelYellow
0 - 18
-
1
G1L01_YELLOW
Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen
0 - 18
-
1
G1L01_GREEN
Label string shown when LED 1, alarm
group 1 is green
5.4
LCD part for HMI function keys control module
5.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
LCD part for HMI Function Keys Control
module
FNKEYMD1 -
FNKEYMD5
-
-
5.4.2
Function block
FNKEYMD1
^LEDCTL1
^FKEYOUT1
IEC09000327 V1 EN
Figure 6:
FNKEYMD1 function block
Only the function block for the first button is shown above. There is a similar block for
every function button.
Section 5
1MRK 504 135-UEN A
Local Human-Machine-Interface LHMI
60
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...