Name
Values (Range)
Unit
Step
Default
Description
Threshold4
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 4
DebounceTime4
0.000 - 0.100
s
0.001
0.005
Debounce time for input 4
OscillationCount4
0 - 255
-
1
0
Oscillation count for input 4
OscillationTime4
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 4
Threshold5
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 5
DebounceTime5
0.000 - 0.100
s
0.001
0.005
Debounce time for input 5
OscillationCount5
0 - 255
-
1
0
Oscillation count for input 5
OscillationTime5
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 5
Threshold6
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 6
DebounceTime6
0.000 - 0.100
s
0.001
0.005
Debounce time for input 6
OscillationCount6
0 - 255
-
1
0
Oscillation count for input 6
OscillationTime6
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 6
Threshold7
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 7
DebounceTime7
0.000 - 0.100
s
0.001
0.005
Debounce time for input 7
OscillationCount7
0 - 255
-
1
0
Oscillation count for input 7
OscillationTime7
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 7
Threshold8
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 8
DebounceTime8
0.000 - 0.100
s
0.001
0.005
Debounce time for input 8
OscillationCount8
0 - 255
-
1
0
Oscillation count for input 8
OscillationTime8
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 8
Threshold9
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 9
DebounceTime9
0.000 - 0.100
s
0.001
0.005
Debounce time for input 9
OscillationCount9
0 - 255
-
1
0
Oscillation count for input 9
OscillationTime9
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 9
Threshold10
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 10
DebounceTime10
0.000 - 0.100
s
0.001
0.005
Debounce time for input 10
OscillationCount10
0 - 255
-
1
0
Oscillation count for input 10
OscillationTime10
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 10
Threshold11
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 11
DebounceTime11
0.000 - 0.100
s
0.001
0.005
Debounce time for input 11
OscillationCount11
0 - 255
-
1
0
Oscillation count for input 11
OscillationTime11
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 11
Threshold12
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 12
Table continues on next page
Section 4
1MRK 504 135-UEN A
Binary input and output modules
54
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...