Name
Values (Range)
Unit
Step
Default
Description
MV lLim
-5000.00 - 5000.00
xBase
0.01
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
MV llLim
-5000.00 - 5000.00
xBase
0.01
-900.00
Low Low limit multiplied with the base
prefix (multiplication factor)
MV min
-5000.00 - 5000.00
xBase
0.01
-1000.00
Minimum value multiplied with the base
prefix (multiplication factor)
MV max
-5000.00 - 5000.00
xBase
0.01
1000.00
Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
MV limHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
14.12.6
Monitored data
Table 392:
MVGGIO Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE
REAL
-
-
Magnitude of deadband
value
RANGE
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
-
Range
14.12.7
Operation principle
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range, as
output values. In the same time, it will send over IEC 61850-8-1 the value, to other IEC
61850 clients in the substation.
14.13
Measured value expander block MVEXP
14.13.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
MVEXP
-
-
1MRK 504 135-UEN A
Section 14
Monitoring
487
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...