12.12.2
Function block
IEC10000285-1-en.vsd
I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285 V1 EN
Figure 161:
I103GENCMD function block
12.12.3
Signals
Table 269:
I103GENCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
Table 270:
I103GENCMD Output signals
Name
Type
Description
CMD_OFF
BOOLEAN
Command output OFF
CMD_ON
BOOLEAN
Command output ON
12.12.4
Settings
Table 271:
I103GENCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseLength
0.000 - 60.000
s
0.001
0.400
Pulse length
InfNo
1 - 255
-
1
1
Information number for command output
(1-255)
12.13
IED commands with position and select for IEC
60870-5-103 I103POSCMD
12.13.1
Functionality
I103POSCMD has double-point position indicators that are getting the position value
as an integer (for example from the POSITION output of the SCSWI function block)
and sending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not
define the use of values 0 and 3 . However, when connected to a switching device,
these values are transmitted.
Section 12
1MRK 504 135-UEN A
Control
368
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...