11.1.5
Settings
Table 170:
SDDRFUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off / On
OpMode
Off
UNsINs
UZsIZs
UZsIZs OR UNsINs
UZsIZs AND
UNsINs
OptimZsNs
-
-
UZsIZs
Operating mode selection
3U0>
1 - 100
%UB
1
30
Operate level of residual overvoltage
element in % of UBase
3I0<
1 - 100
%IB
1
10
Operate level of residual undercurrent
element in % of IBase
3U2>
1 - 100
%UB
1
30
Operate level of neg seq overvoltage
element in % of UBase
3I2<
1 - 100
%IB
1
10
Operate level of neg seq undercurrent
element in % of IBase
OpDUDI
Off
On
-
-
Off
Operation of change based function
Off/On
DU>
1 - 100
%UB
1
60
Operate level of change in phase voltage
in % of UBase
DI<
1 - 100
%IB
1
15
Operate level of change in phase current
in % of IBase
UPh>
1 - 100
%UB
1
70
Operate level of phase voltage in % of
UBase
IPh>
1 - 100
%IB
1
10
Operate level of phase current in % of
IBase
SealIn
Off
On
-
-
On
Seal in functionality Off/On
USealln<
1 - 100
%UB
1
70
Operate level of seal-in phase voltage in
% of UBase
IDLD<
1 - 100
%IB
1
5
Operate level for open phase current
detection in % of IBase
UDLD<
1 - 100
%UB
1
60
Operate level for open phase voltage
detection in % of UBase
Table 171:
SDDRFUF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
1MRK 504 135-UEN A
Section 11
Secondary system supervision
245
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...