11.1.8
Technical data
Table 173:
SDDRFUF technical data
Function
Range or value
Accuracy
Operate voltage, zero sequence
(1-100)% of UBase
± 1.0% of U
r
Operate current, zero sequence
(1–100)% of IBase
± 1.0% of I
r
Operate voltage, negative sequence
(1–100)% of UBase
± 0.5% of U
r
Operate current, negative sequence
(1–100)% of IBase
± 1.0% of I
r
Operate voltage change level
(1–100)% of UBase
± 5.0% of U
r
Operate current change level
(1–100)% of IBase
± 5.0% of I
r
Operate phase voltage
(1-100)% of UBase
± 0.5% of U
r
Operate phase current
(1-100)% of IBase
± 1.0% of I
r
Operate phase dead line voltage
(1-100)% of UBase
± 0.5% of U
r
Operate phase dead line current
(1-100)% of IBase
± 1.0% of I
r
11.2
Breaker close/trip circuit monitoring TCSSCBR
11.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker close/trip circuit monitoring
TCSSCBR
-
-
11.2.2
Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The trip circuit supervision generates a current of
approximately 1 mA through the supervised control circuit. The validity supervision
of a control circuit is provided for power output contacts T1, T2 and T3.
The trip circuit supervision operates after a settable definite operating time and resets
after a settable definite time when the fault disappears.
11.2.3
Function block
GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 115:
Function block
Section 11
1MRK 504 135-UEN A
Secondary system supervision
254
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...