Stabilization is included for inrush and overexcitation currents respectively, cross-
blocking is also available. Adaptive stabilization is also included for system recovery
inrush and CT saturation during external faults. A high set unrestrained differential
current protection element is included for a very high speed tripping at a high internal
fault currents.
Included is an innovative sensitive differential protection element based on the theory
of symmetrical components. This element offers the best possible coverage of power
transformer windings turn to turn faults.
6.1.2
Transformer differential protection, two winding T2WPDIF
6.1.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Transformer differential protection, two-
winding
T2WPDIF
3Id/I
SYMBOL-BB V1 EN
87T
6.1.2.2
Function block
T2WPDIF
I3PW1CT1*
I3PW2CT1*
BLOCK
TRIP
TRIPRES
TRIPUNRE
TRNSUNR
TRNSSENS
START
STL1
STL2
STL3
BLK2H
BLK5H
BLKWAV
IDALARM
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC09000274_1_en.vsd
IEC09000274 V1 EN
Figure 30:
T2WPDIF function block
6.1.2.3
Signals
Table 24:
T2WPDIF Input signals
Name
Type
Default
Description
I3PW1CT1
GROUP
SIGNAL
-
Three phase current connection winding 1 (W1)
CT1
I3PW2CT1
GROUP
SIGNAL
-
Three phase current connection winding 2 (W2)
CT1
BLOCK
BOOLEAN
0
Block of function
Section 6
1MRK 504 135-UEN A
Differential protection
80
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...