9.3.8
Technical data
Table 147:
ROV2PTOV technical data
Function
Range or value
Accuracy
Operate voltage,
step 1
(1-200)% of
UBase
± 0.5% of U
r
at U < U
r
± 0.5% of U at U > U
r
Operate voltage,
step 2
(1–100)% of
UBase
± 0.5% of U
r
at U < U
r
± 0.5% of U at U > U
r
Reset ratio
> 98%
-
Inverse time
characteristics for
low and high step,
-
Definite time setting,
step 1
(0.00–6000.00) s
± 0.5% ± 25 ms
Definite time setting,
step 2
(0.000–60.000) s
± 0.5% ± 25 ms
Minimum operate
time for step 1
inverse characteristic
(0.000-60.000) s
± 0.5% ± 25 ms
Operate time, start
function
30 ms typically at 0 to 2 x U
set
-
Reset time, start
function
40 ms typically at 2 to 0 x U
set
-
Critical impulse time
10 ms typically at 0 to 1.2 xU
set
-
Impulse margin time
15 ms typically
-
9.4
Overexcitation protection OEXPVPH
9.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Overexcitation protection
OEXPVPH
U/f >
SYMBOL-Q V1 EN
24
9.4.2
Functionality
When the laminated core of a power transformer or generator is subjected to a
magnetic flux density beyond its design limits, stray flux will flow into non-laminated
components that are not designed to carry flux. This will cause eddy currents to flow.
These eddy currents can cause excessive heating and severe damage to insulation and
1MRK 504 135-UEN A
Section 9
Voltage protection
221
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...