Name
Values (Range)
Unit
Step
Default
Description
UnderTrigOp03
Off
On
-
-
Off
Use under level trigger for analog channel
3 (on) or not (off)
UnderTrigLe03
0 - 200
%
1
50
Under trigger level for analog channel 3 in
% of signal
OverTrigOp03
Off
On
-
-
Off
Use over level trigger for analog channel 3
(on) or not (off)
OverTrigLe03
0 - 5000
%
1
200
Overtrigger level for analog channel 3 in %
of signal
NomValue04
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 4
UnderTrigOp04
Off
On
-
-
Off
Use under level trigger for analog channel
4 (on) or not (off)
UnderTrigLe04
0 - 200
%
1
50
Under trigger level for analog channel 4 in
% of signal
OverTrigOp04
Off
On
-
-
Off
Use over level trigger for analog channel 4
(on) or not (off)
OverTrigLe04
0 - 5000
%
1
200
Over trigger level for analog channel 4 in
% of signal
NomValue05
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 5
UnderTrigOp05
Off
On
-
-
Off
Use under level trigger for analog channel
5 (on) or not (off)
UnderTrigLe05
0 - 200
%
1
50
Under trigger level for analog channel 5 in
% of signal
OverTrigOp05
Off
On
-
-
Off
Use over level trigger for analog channel 5
(on) or not (off)
OverTrigLe05
0 - 5000
%
1
200
Over trigger level for analog channel 5 in
% of signal
NomValue06
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 6
UnderTrigOp06
Off
On
-
-
Off
Use under level trigger for analog channel
6 (on) or not (off)
UnderTrigLe06
0 - 200
%
1
50
Under trigger level for analog channel 6 in
% of signal
OverTrigOp06
Off
On
-
-
Off
Use over level trigger for analog channel 6
(on) or not (off)
OverTrigLe06
0 - 5000
%
1
200
Over trigger level for analog channel 6 in
% of signal
NomValue07
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 7
UnderTrigOp07
Off
On
-
-
Off
Use under level trigger for analog channel
7 (on) or not (off)
UnderTrigLe07
0 - 200
%
1
50
Under trigger level for analog channel 7 in
% of signal
OverTrigOp07
Off
On
-
-
Off
Use over level trigger for analog channel 7
(on) or not (off)
OverTrigLe07
0 - 5000
%
1
200
Over trigger level for analog channel 7 in
% of signal
NomValue08
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 8
UnderTrigOp08
Off
On
-
-
Off
Use under level trigger for analog channel
8 (on) or not (off)
Table continues on next page
Section 14
1MRK 504 135-UEN A
Monitoring
454
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...