Table 467:
RS485103 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SlaveAddress
1 - 255
-
1
1
Slave address
BaudRate
9600 Bd
19200 Bd
-
-
9600 Bd
Baudrate on serial line
CycMeasRepTime
1.0 - 1800.0
s
0.1
5.0
Cyclic reporting time of measurments
MasterTimeDomain
UTC
Local
Local with DST
-
-
UTC
Master time domain
TimeSyncMode
IEDTime
LinMastTime
IEDTimeSkew
-
-
IEDTime
Time synchronization mode
EvalTimeAccuracy
Off
5ms
10ms
20ms
40ms
-
-
5ms
Evaluate time accuracy for invalid time
EventRepMode
SeqOfEvent
HiPriSpont
-
-
SeqOfEvent
Event reporting mode
16.12
IEC 61850-8-1 redundant station bus communication
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
System component for parallel
redundancy protocol
PRPSTATUS
-
-
16.12.1
Functionality
Redundant station bus communication according to IEC 62439-3 Edition 2 is
available as option in the Customized 650 Ver 1.3 series IEDs, and the selection is
made at ordering. Redundant station bus communication according to IEC 62439-3
Edition 2 uses both ports LAN1A and LAN1B on the COM03 module.
Select COM03 for redundant station bus according to IEC 62439-3
Edition 2 protocol, at the time of ordering.
IEC 62439-3 Edition 2 is NOT compatible with IEC 62439-3 Edition
1.
16.12.2
Principle of operation
The redundant station bus communication is configured using the local HMI,
Main
Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB
.
The settings are also visible in PST in PCM600.
1MRK 504 135-UEN A
Section 16
Station communication
551
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...