14.3.5
Signals
Table 363:
L4UFCNT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
INPUT
BOOLEAN
0
Input for counter
RESET
BOOLEAN
0
Reset of function
Table 364:
L4UFCNT Output signals
Name
Type
Description
ERROR
BOOLEAN
Error indication on counter limit and/or initial value
settings
OVERFLOW
BOOLEAN
Overflow indication on count of greater than
MaxValue
LIMIT1
BOOLEAN
Counted value is larger than or equal to
CounterLimit1
LIMIT2
BOOLEAN
Counted value is larger than or equal to
CounterLimit2
LIMIT3
BOOLEAN
Counted value is larger than or equal to
CounterLimit3
LIMIT4
BOOLEAN
Counted value is larger than or equal to
CounterLimit4
VALUE
INTEGER
Counted value
14.3.6
Settings
Table 365:
L4UFCNT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
CountType
Set
Reset
Both
-
-
Set
Select counting on positive and/or
negative flanks
CounterLimit1
1 - 65535
-
1
100
Value of the first limit
CounterLimit2
1 - 65535
-
1
200
Value of the second limit
CounterLimit3
1 - 65535
-
1
300
Value of the third limit
CounterLimit4
1 - 65535
-
1
400
Value of the fourth limit
MaxValue
1 - 65535
-
1
500
Maximum count value
OnMaxValue
Stop
Rollover Steady
Rollover Pulsed
-
-
Stop
Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
InitialValue
0 - 65535
-
1
0
Initial count value after reset of the
function
Section 14
1MRK 504 135-UEN A
Monitoring
444
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...