Name
Values (Range)
Unit
Step
Default
Description
Latched7
Pulsed
Latched
-
-
Pulsed
Setting for pulsed/latched mode for output
7
tPulse7
0.01 - 6000.00
s
0.01
0.10
Output 7 Pulse Time
Latched8
Pulsed
Latched
-
-
Pulsed
Setting for pulsed/latched mode for output
8
tPulse8
0.01 - 6000.00
s
0.01
0.10
Output 8 pulse time
12.7.6
Operation principle
The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the
eight outputs is activated based on the command sent from the operator place selected.
The settings
Latchedx
and
tPulsex
(where x is the respective output) will determine if
the signal will be pulsed (and how long the pulse is) or latched (steady). BLOCK will
block the operation of the function – in case a command is sent, no output will be
activated.
PSTO is the universal operator place selector for all control functions.
Although, PSTO can be configured to use LOCAL or ALL operator
places only, REMOTE operator place is used in SPC8GGIO function.
12.8
Automation bits AUTOBITS
12.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
AutomationBits, command function for
DNP3
AUTOBITS
-
-
12.8.2
Functionality
The Automation bits function AUTOBITS is used to configure the DNP3 protocol
command handling. Each of the 3 AUTOBITS available has 32 individual outputs
available, each can be mapped as a binary output point in DNP3.
1MRK 504 135-UEN A
Section 12
Control
361
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...