Name
Type
Description
I2
REAL
I2 Amplitude
I2RANG
INTEGER
I2 Amplitude range
I2ANGL
REAL
I2Angle
14.1.5.4
Settings
Table 344:
CMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
3I0DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3I0Min
0 - 500000
A
1
0
Minimum value
3I0Max
0 - 500000
A
1
3300
Maximum value
3I0RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
3I0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1Min
0 - 500000
A
1
0
Minimum value
I1Max
0 - 500000
A
1
1300
Maximum value
I1RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2Min
0 - 500000
A
1
0
Minimum value
I2Max
0 - 500000
A
1
1300
Maximum value
I2RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
I2AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
1MRK 504 135-UEN A
Section 14
Monitoring
421
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...