Function
Range or value
Accuracy
Apparent power, S
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
± 1.0% of S
r
at S ≤ S
r
± 1.0% of S at S > S
r
Apparent power, S Three phase
settings
cos phi = 1
± 0.5% of S at S > S
r
± 0.5% of S
r
at S ≤ S
r
Power factor, cos (φ)
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
< 0.02
14.2
Event Counter CNTGGIO
14.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter
CNTGGIO
S00946 V1 EN
-
14.2.2
Functionality
Event counter CNTGGIO has six counters which are used for storing the number of
times each counter input has been activated.
14.2.3
Function block
CNTGGIO
BLOCK
COUNTER1
COUNTER2
COUNTER3
COUNTER4
COUNTER5
COUNTER6
RESET
VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6
IEC09000090_1_en.vsd
IEC09000090 V1 EN
Figure 197:
CNTGGIO function block
14.2.4
Signals
Table 358:
CNTGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
COUNTER1
BOOLEAN
0
Input for counter 1
COUNTER2
BOOLEAN
0
Input for counter 2
COUNTER3
BOOLEAN
0
Input for counter 3
COUNTER4
BOOLEAN
0
Input for counter 4
Table continues on next page
1MRK 504 135-UEN A
Section 14
Monitoring
439
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...