10.1.4
Signals
Table 154:
SAPTUF Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
Table 155:
SAPTUF Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
START
BOOLEAN
General start signal
RESTORE
BOOLEAN
Restore signal for load restoring purposes
BLKDMAGN
BOOLEAN
Measurement blocked due to low voltage
amplitude
10.1.5
Settings
Table 156:
SAPTUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
StartFrequency
35.00 - 75.00
Hz
0.01
48.80
Frequency set value
tDelay
0.000 - 60.000
s
0.001
0.200
Operate time delay
tRestore
0.000 - 60.000
s
0.001
0.000
Restore time delay
RestoreFreq
45.00 - 65.00
Hz
0.01
49.90
Restore frequency if frequency is above
frequency value
10.1.6
Monitored data
Table 157:
SAPTUF Monitored data
Name
Type
Values (Range)
Unit
Description
FREQ
REAL
-
Hz
Measured frequency
10.1.7
Operation principle
The underfrequency protection (SAPTUF) function is used to detect low power
system frequency. If the frequency remains below the set value for a time period
greater than the set time delay the TRIP signal is issued. To avoid an unwanted trip due
to uncertain frequency measurement at low voltage magnitude, a voltage controlled
blocking of the function is available from the preprocessing function, that is, if the
Section 10
1MRK 504 135-UEN A
Frequency protection
232
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...