Name
Values (Range)
Unit
Step
Default
Description
UnderTrigLe08
0 - 200
%
1
50
Under trigger level for analog channel 8 in
% of signal
OverTrigOp08
Off
On
-
-
Off
Use over level trigger for analog channel 8
(on) or not (off)
OverTrigLe08
0 - 5000
%
1
200
Over trigger level for analog channel 8 in
% of signal
NomValue09
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 9
UnderTrigOp09
Off
On
-
-
Off
Use under level trigger for analog channel
9 (on) or not (off)
UnderTrigLe09
0 - 200
%
1
50
Under trigger level for analog channel 9 in
% of signal
OverTrigOp09
Off
On
-
-
Off
Use over level trigger for analog channel 9
(on) or not (off)
OverTrigLe09
0 - 5000
%
1
200
Over trigger level for analog channel 9 in
% of signal
NomValue10
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 10
UnderTrigOp10
Off
On
-
-
Off
Use under level trigger for analog channel
10 (on) or not (off)
UnderTrigLe10
0 - 200
%
1
50
Under trigger level for analog channel 10
in % of signal
OverTrigOp10
Off
On
-
-
Off
Use over level trigger for analog channel
10 (on) or not (off)
OverTrigLe10
0 - 5000
%
1
200
Over trigger level for analog channel 10 in
% of signal
14.4.4
Analog input signals A4RADR
14.4.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Analog input signals
A4RADR
-
-
14.4.4.2
Function block
A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40
IEC09000350-1-en.vsd
IEC09000350 V1 EN
Figure 202:
A4RADR function block, derived analog inputs
1MRK 504 135-UEN A
Section 14
Monitoring
455
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...