8.8.3.3
Signals
Table 116:
GUPPDUP Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKST1
BOOLEAN
0
Block of step 1
BLKST2
BOOLEAN
0
Block of step 2
Table 117:
GUPPDUP Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TRIP1
BOOLEAN
Trip signal from stage 1
TRIP2
BOOLEAN
Trip signal from stage 2
START
BOOLEAN
General start signal
START1
BOOLEAN
Start signal from stage 1
START2
BOOLEAN
Start signal from stage 2
P
REAL
Active Power
PPERCENT
REAL
Active power in % of calculated power base value
Q
REAL
Reactive power
QPERCENT
REAL
Reactive power in % of calculated power base
value
8.8.3.4
Settings
Table 118:
GUPPDUP Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OpMode1
Off
UnderPower
-
-
UnderPower
Operation mode 1
Power1
0.0 - 500.0
%
0.1
1.0
Power setting for stage 1 in % of
calculated power base value
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 1
TripDelay1
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 1
OpMode2
Off
UnderPower
-
-
UnderPower
Operation mode 2
Power2
0.0 - 500.0
%
0.1
1.0
Power setting for stage 2 in % of
calculated power base value
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 2
TripDelay2
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 2
1MRK 504 135-UEN A
Section 8
Current protection
193
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...