Table 524:
Binary inputs X339, 3U full 19”
Terminal
Description
PCM600 info
Hardware module
instance
Hardware channel
X339-1
- for input 1
BIO_6
BI1
X339-2
Binary input 1 +
BIO_6
BI1
X339-3
-
X339-4
Common - for inputs 2-3
X339-5
Binary input 2 +
BIO_6
BI2
X339-6
Binary input 3 +
BIO_6
BI3
X339-7
-
X339-8
Common - for inputs 4-5
X339-9
Binary input 4 +
BIO_6
BI4
X339-10
Binary input 5 +
BIO_6
BI5
X339-11
-
X339-12
Common - for inputs 6-7
X339-13
Binary input 6 +
BIO_6
BI6
X339-14
Binary input 7 +
BIO_6
BI7
X339-15
-
X339-16
Common - for inputs 8-9
X339-17
Binary input 8 +
BIO_6
BI8
X339-18
Binary input 9 +
BIO_6
BI9
18.3
Outputs
18.3.1
Outputs for tripping, controlling and signalling
Output contacts PO1, PO2 and PO3 are power output contacts used, for example, for
controlling circuit breakers.
Each signal connector terminal is connected with one 0.5...2.5 mm
2
wire or with two
0.5...1.0 mm
2
wires.
The connected DC voltage to outputs with trip circuit supervision
(TCS) must have correct polarity or the trip circuit supervision
TCSSCBR function will not operate properly.
Section 18
1MRK 504 135-UEN A
IED physical connections
606
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...