select
tSelect
timer
execute command
t1
t1>tSelect, then long-
operation-time in 'cause'
is set
en05000092.vsd
IEC05000092 V1 EN
Figure 123:
tSelect
The timer
tExecutionFB
supervises the time between the execute command and the
command termination, see figure
.
execute command
position L1
t1>tExecutionFB, then
long-operation-time in
'cause' is set
open
close
close
open
position L3
close
open
position L2
t1
tExecutionFB
timer
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination
position
open
close
* The cmd termination will be delayed one execution sample.
*
en05000094.vsd
IEC05000094 V1 EN
Figure 124:
tExecutionFB
The parameter
tSynchrocheck
is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true at
the time the execute command signal is received, the timer "tSynchrocheck" will not
start. The start signal for the synchronizing is obtained if the synchrocheck conditions
are not fulfilled.
Section 12
1MRK 504 135-UEN A
Control
270
Technical manual