Table 233:
TCMYLTC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
LowVoltTap
1 - 63
-
1
1
Tap position for the lowest voltage
HighVoltTap
1 - 63
-
1
33
Tap position for the highest voltage
mALow
0.000 - 25.000
mA
0.001
4.000
mA for the lowest voltage tap position
mAHigh
0.000 - 25.000
mA
0.001
20.000
mA for the highest voltage tap position
CodeType
Binary
BCD
Gray
ContactPerTap
mA
-
-
Binary
Type of code conversion
UseParity
Off
On
-
-
Off
Enable parity check
tStable
1 - 60
s
1
2
Time after position change before the
value is accepted
CLFactor
1.0 - 3.0
-
0.1
2.0
Adjustable factor for contact life function
InitCLCounter
0 - 9999999
s
1
250000
CL counter start value
EnabTapCmd
Off
On
-
-
On
Enable commands to tap changer
12.3.3.5
Monitored data
Table 234:
TCMYLTC Monitored data
Name
Type
Values (Range)
Unit
Description
CNT_VAL
INTEGER
-
-
Number of operations on
tap changer
CLCNT_VAL
REAL
-
-
Remaining number of
operations at rated load
TCPOS
INTEGER
-
-
Integer value
corresponding to actual
tap position
12.3.4
Operation principle
The voltage control function is built up by two function blocks. Both are logical nodes
in IEC 61850-8-1.
•
Automatic voltage control for tap changer
•
TR8ATCC
•
Tap changer control and supervision
•
TCMYLTC, 6 binary inputs
1MRK 504 135-UEN A
Section 12
Control
341
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...