10.3.7
Technical data
Table 167:
SAPFRC technical data
Function
Range or value
Accuracy
Operate value, start function
(-10.00-10.00) Hz/s
± 10.0 mHz/s
Operate value, restore
enable frequency
(45.00 - 65.00) Hz
± 2.0 mHz
Timers
(0.000 - 60.000) s
<130 ms
Operate time, start function
At 50 Hz: 100 ms typically
At 60 Hz: 80 ms typically
-
Section 10
1MRK 504 135-UEN A
Frequency protection
242