Name
Values (Range)
Unit
Step
Default
Description
AccCurrAlmLvl
0.00 - 20000.00
-
0.01
2500.00
Setting of alarm level for accumulated
currents power
AccCurrLO
0.00 - 20000.00
-
0.01
2500.00
Lockout limit setting for accumulated
currents power
DirCoef
-3.00 - -0.50
-
0.01
-1.50
Directional coefficient for CB life
calculation
LifeAlmLevel
0 - 99999
-
1
5000
Alarm level for CB remaining life
OpNumRatCurr
1 - 99999
-
1
10000
Number of operations possible at rated
current
OpNumFaultCurr
1 - 10000
-
1
1000
Number of operations possible at rated
fault current
OpNumAlm
0 - 9999
-
1
200
Alarm limit for number of operations
OpNumLO
0 - 9999
-
1
300
Lockout limit for number of operations
tOpenAlm
0 - 200
ms
1
40
Alarm level setting for open travel time
tCloseAlm
0 - 200
ms
1
40
Alarm level setting for close travel time
OpenTimeCorr
0 - 100
ms
1
10
Correction factor for open travel time
CloseTimeCorr
0 - 100
ms
1
10
Correction factor for CB close travel time
DifTimeCorr
-10 - 10
ms
1
5
Correction factor for time difference in
auxiliary and main contacts open time
tSprngChrgAlm
0.00 - 60.00
s
0.01
1.00
Setting of alarm for spring charging time
tPressAlm
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure alarm
TPressLO
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure lockout
AccEnerInitVal
0.00 - 9999.99
-
0.01
0.00
Accumulation energy initial value
CountInitVal
0 - 9999
-
1
0
Operation numbers counter initialization
value
CBRemLife
0 - 9999
-
1
5000
Initial value for the CB remaining life
estimates
InactDayAlm
0 - 9999
Day
1
2000
Alarm limit value of the inactive days
counter
InactDayInit
0 - 9999
Day
1
0
Initial value of the inactive days counter
InactHourAlm
0 - 23
Hour
1
0
Alarm time of the inactive days counter in
hours
14.17.6
Monitored data
Table 413:
SSCBR Monitored data
Name
Type
Values (Range)
Unit
Description
CBOTRVT
REAL
-
ms
Travel time of the CB
during opening operation
CBCLTRVT
REAL
-
ms
Travel time of the CB
during closing operation
SPRCHRT
REAL
-
s
The charging time of the
CB spring
NO_OPR
INTEGER
-
-
Number of CB operation
cycle
Table continues on next page
Section 14
1MRK 504 135-UEN A
Monitoring
500
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...