14.1.3.2
Function block
The available function blocks of an IED are depending on the actual hardware (TRM)
and the logic configuration made in PCM600.
CMMXU
I3P
IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
IEC08000225 V1 EN
Figure 186:
CMMXU function block
14.1.3.3
Signals
Table 332:
CMMXU Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
Table 333:
CMMXU Output signals
Name
Type
Description
IL1
REAL
IL1 Amplitude
IL1RANG
INTEGER
IL1 Amplitude range
IL1ANGL
REAL
IL1 Angle
IL2
REAL
IL2 Amplitude
IL2RANG
INTEGER
IL2 Amplitude range
IL2ANGL
REAL
IL2 Angle
IL3
REAL
IL3 Amplitude
IL3RANG
INTEGER
IL3 Amplitude range
IL3ANGL
REAL
IL3 Angle
14.1.3.4
Settings
Table 334:
CMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
ILDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table continues on next page
Section 14
1MRK 504 135-UEN A
Monitoring
416
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...