14.16.4
Signals
Inputs LEVEL and TEMP together with settings
LevelAlmLimit
,
LevelLOLimit
,
TempAlarmLimit
and
TempLOLimit
are not supported
in this release of 650 series.
Table 406:
SSIML Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
BLK_ALM
BOOLEAN
0
Block all the alarms
LEVEL
REAL
0.0
Level input from CB
TEMP
REAL
0.0
Temperature of the insulation medium from CB
LVL_ALM
BOOLEAN
0
Level alarm signal
LEVEL_LO
BOOLEAN
0
Level lockout signal
SET_L_LO
BOOLEAN
0
Set level lockout
SET_T_LO
BOOLEAN
0
Set temperature lockout
RESET_LO
BOOLEAN
0
Reset level and temperature lockout
Table 407:
SSIML Output signals
Name
Type
Description
LEVEL
REAL
Level service value
LVL_ALM
BOOLEAN
Level below alarm level
LVL_LO
BOOLEAN
Level below lockout level
TEMP
REAL
Temperature of the insulation medium
TEMP_ALM
BOOLEAN
Temperature above alarm level
TEMP_LO
BOOLEAN
Temperature above lockout level
14.16.5
Settings
Table 408:
SSIML Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
LevelAlmLimit
0.00 - 25.00
-
0.01
5.00
Alarm setting for level
LevelLOLimit
0.00 - 25.00
-
0.01
3.00
Level lockout setting
TempAlarmLimit
-40.00 - 200.00
-
0.01
30.00
Temperature alarm level setting of the
medium
TempLOLimit
-40.00 - 200.00
-
0.01
30.00
Temperature lockout level of the medium
tLevelAlarm
0.000 - 60.000
s
0.001
0.000
Time delay for level alarm
tLevelLockOut
0.000 - 60.000
s
0.001
0.000
Time delay for level lockout indication
Table continues on next page
Section 14
1MRK 504 135-UEN A
Monitoring
496
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...