Section 10
Frequency protection
10.1
Underfrequency protection SAPTUF
10.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Underfrequency protection
SAPTUF
f <
SYMBOL-P V1 EN
81
10.1.2
Functionality
Underfrequency occurs as a result of a lack of sufficient generation in the network.
Underfrequency protection SAPTUF measures frequency with high accuracy, and is
used for load shedding systems, remedial action schemes, gas turbine startup and so
on. Separate definite time delays are provided for operate and restore.
SAPTUF is provided with undervoltage blocking.
10.1.3
Function block
SAPTUF
U3P*
BLOCK
TRIP
START
RESTORE
BLKDMAGN
IEC09000282_1_en.vsd
IEC09000282 V1 EN
Figure 102:
SAPTUF function block
1MRK 504 135-UEN A
Section 10
Frequency protection
231
Technical manual