14.14.6
Measured values
Table 399:
SPVNZBAT Measured values
Name
Type
Default
Description
U_BATT
REAL
0.00
Battery terminal voltage that has to be supervised
BLOCK
BOOLEAN
0
Blocks all the output signals of the function
14.14.7
Monitored Data
Table 400:
SPVNZBAT Monitored data
Name
Type
Values (Range)
Unit
Description
BATTVOLT
REAL
-
kV
Service value of the
battery terminal voltage
14.14.8
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The function execution requires that at least one of the function
outputs is connected in configuration.
The operation of the station battery supervision function can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.
GUID-9ACD1EE5-61C1-4CB8-9AF0-6F43292FC547 V2 EN
Figure 212:
Functional module diagram
The battery rated voltage is set with the
RtdBattVolt
setting. The value of the
BattVoltLowLim
and
BattVoltHiLim
settings are given in relative per unit to the
RtdBattVolt
setting.
It is possible to block the function outputs by the
BLOCK
input.
1MRK 504 135-UEN A
Section 14
Monitoring
491
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...