12.1.5
Bay control QCBAY
12.1.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Bay control
QCBAY
-
-
12.1.5.2
Functionality
The Bay control QCBAY function is used together with Local remote and local
remote control functions to handle the selection of the operator place per bay. QCBAY
also provides blocking functions that can be distributed to different apparatuses within
the bay.
12.1.5.3
Function block
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 118:
QCBAY function block
12.1.5.4
Signals
Table 187:
QCBAY Input signals
Name
Type
Default
Description
LR_OFF
BOOLEAN
0
External Local/Remote switch is in Off position
LR_LOC
BOOLEAN
0
External Local/Remote switch is in Local position
LR_REM
BOOLEAN
0
External Local/Remote switch is in Remote
position
LR_VALID
BOOLEAN
0
Data representing the L/R switch position is valid
BL_UPD
BOOLEAN
0
Steady signal to block the position updates
BL_CMD
BOOLEAN
0
Steady signal to block the command
Table 188:
QCBAY Output signals
Name
Type
Description
PSTO
INTEGER
Value for the operator place allocation
UPD_BLKD
BOOLEAN
Update of position is blocked
CMD_BLKD
BOOLEAN
Function is blocked for commands
LOC
BOOLEAN
Local operation allowed
REM
BOOLEAN
Remote operation allowed
Section 12
1MRK 504 135-UEN A
Control
262
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...