Table 517:
Auxiliary voltage supply of 110...250 V DC or 100...240 V AC
Case
Terminal
Description
3U full 19”
X420-1
- Input
X420-3
+ Input
Table 518:
Auxiliary voltage supply of 48-125 V DC
Case
Terminal
Description
3U full 19”
X420-1
- Input
X420-2
+ Input
Table 519:
Auxiliary voltage supply of 24-30 V DC
Case
Terminal
Description
3U full 19”
X420-3
- Input
X420-2
+ Input
18.2.3
Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch
output contacts, to trigger the disturbance recorder or for remote control of IED
settings.
Each signal connector terminal is connected with one 0.5...2.5 mm
2
wire or with two
0.5...1.0 mm
2
wires.
Table 520:
Binary inputs X304, 3U full 19”
Terminal
Description
PCM600 info
Hardware module
instance
Hardware channel
X304-1
Common - for inputs 1-3
X304-2
Binary input 1 +
COM_101
BI1
X304-3
Binary input 2 +
COM_101
BI2
X304-4
Binary input 3 +
COM_101
BI3
X304-5
Common - for inputs 4-6
X304-6
Binary input 4 +
COM_101
BI4
X304-7
Binary input 5 +
COM_101
BI5
X304-8
Binary input 6 +
COM_101
BI6
X304-9
Common - for inputs 7-9
X304-10
Binary input 7 +
COM_101
BI7
X304-11
Binary input 8 +
COM_101
BI8
X304-12
Binary input 9 +
COM_101
BI9
Table continues on next page
1MRK 504 135-UEN A
Section 18
IED physical connections
603
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...