The remaining life is calculated separately for all three phases and it is available as a
monitored data value
CBLIFEL1 (L2, L3)
. The values can be cleared by setting
the parameter
CB wear values
in the clear menu from LHMI.
Clearing
CB wear values
also resets the operation counter.
Alarm limit check
When the remaining life of any phase drops below the
LifeAlmLevel
threshold setting,
the corresponding circuit breaker life alarm
CBLIFEAL
is activated.
It is possible to deactivate the
CBLIFEAL
alarm signal by activating the binary input
BLOCK
. The old circuit breaker operation counter value can be taken into use by
writing the value to the
Initial CB Rmn life
parameter and resetting the value via the
clear menu from LHMI.
It is possible to deactivate the
CBLIFEAL
alarm signal by activating the binary input
BLOCK
.
14.17.7.7
Circuit breaker spring charged indication
The circuit breaker spring charged indication subfunction calculates the spring
charging time.
The operation of the subfunction can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
GUID-37EB9FAE-8129-45AB-B9F7-7F7DC829E3ED V1 EN
Figure 224:
Functional module diagram for circuit breaker spring charged
indication and alarm
Spring charge time measurement
Two binary inputs,
SPRCHRGN
and
SPRCHRGD
, indicate spring charging started and
spring charged, respectively. The spring charging time is calculated from the
difference of these two signal timings.
The spring charging time
SPRCHRT
is available through the Monitored data view .
1MRK 504 135-UEN A
Section 14
Monitoring
509
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...