6.1.5
Technical data
Table 35:
T2WPDIF, T3WPDIF technical data
Function
Range or value
Accuracy
Operating characteristic
Adaptable
± 1.0% of Ir for I < Ir
± 1.0% of I for I > Ir
Reset ratio
>94%
-
Unrestrained differential current limit
(1.00-50.00)x
IBase on
high voltage winding
± 1.0% of set value
Base sensitivity function
(0.05 - 0.60) x
IBase
± 1.0% of Ir
Minimum negative sequence current
(0.02 - 0.20) x
IBase
± 1.0% of Ir
Operate angle, negative sequence
(30.0 - 90.0) degrees
± 1.0 degrees
Second harmonic blocking
(5.0-100.0)% of
fundamental differential
current
± 2.0% of applied harmonic
magnitude
Fifth harmonic blocking
(5.0-100.0)% of
fundamental differential
current
± 12.0% of applied harmonic
magnitude
Connection type for each of the windings
Y or D
-
Phase displacement between high voltage
winding, W1 and each of the windings, W2
and W3. Hour notation
0–11
-
Operate time, restrained function
25 ms typically at 0 to 5
x set level
-
Reset time, restrained function
25 ms typically at 5 to 0
x set level
-
Operate time, unrestrained function
20 ms typically at 0 to 5
x set level
-
Reset time, unrestrained function
25 ms typically at 5 to 0
x set level
-
6.2
Restricted earth-fault protection, low impedance
REFPDIF
6.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Restricted earth-fault protection, low
impedance
REFPDIF
IdN/I
SYMBOL-AA V1 EN
87N
Section 6
1MRK 504 135-UEN A
Differential protection
110
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...