11.1.7.3
Dead line detection
A simplified diagram for the functionality is found in figure
. A dead phase
condition is indicated if both the voltage and the current in one phase is below their
respective setting values
UDLD<
and
IDLD<
. If at least one phase is considered to be
dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated. If all
three phases are considered to be dead the output DLD3PH is activated
IL1
IL2
IL3
a
b
a<b
a
b
a<b
a
b
a<b
IDLD<
UL1
UL2
UL3
a
b
a<b
a
b
a<b
a
b
a<b
UDLD<
OR
AND
AND
AND
AND
AND
AND
AND
AllCurrLow
DeadLineDet1Ph
DLD3PH
DLD1PH
intBlock
Dead Line Detection
IEC10000035-1-en.vsd
IEC10000035 V2 EN
Figure 113:
Simplified logic diagram for Dead Line detection part
11.1.7.4
Main logic
A simplified diagram for the functionality is found in figure
. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting parameter
Operation
to
On
or
Off
.
For increased flexibility and adaptation to system requirements an operation mode
selector,
OpMode
, has been introduced to make it possible to select different operating
modes for the negative and zero sequence based algorithms. The different operation
modes are:
•
Off
. The negative and zero sequence function is switched off.
•
UNsINs
. Negative sequence is selected.
•
UZsIZs
. Zero sequence is selected.
Section 11
1MRK 504 135-UEN A
Secondary system supervision
250
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...