15.2.3
Function block
ETPMMTR
P
Q
STACC
RSTACC
RSTDMD
ACCST
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC09000104 V1 EN
Figure 237:
ETPMMTR function block
15.2.4
Signals
Table 436:
ETPMMTR Input signals
Name
Type
Default
Description
P
REAL
0
Measured active power
Q
REAL
0
Measured reactive power
STACC
BOOLEAN
0
Start to accumulate energy values
RSTACC
BOOLEAN
0
Reset of accumulated enery reading
RSTDMD
BOOLEAN
0
Reset of maximum demand reading
Table 437:
ETPMMTR Output signals
Name
Type
Description
ACCST
BOOLEAN
Start of accumulating energy values
EAFPULSE
BOOLEAN
Accumulated forward active energy pulse
EARPULSE
BOOLEAN
Accumulated reverse active energy pulse
ERFPULSE
BOOLEAN
Accumulated forward reactive energy pulse
ERRPULSE
BOOLEAN
Accumulated reverse reactive energy pulse
EAFALM
BOOLEAN
Alarm for active forward energy exceed limit in set
interval
EARALM
BOOLEAN
Alarm for active reverse energy exceed limit in set
interval
ERFALM
BOOLEAN
Alarm for reactive forward energy exceed limit in
set interval
ERRALM
BOOLEAN
Alarm for reactive reverse energy exceed limit in
set interval
EAFACC
REAL
Accumulated forward active energy value
Table continues on next page
1MRK 504 135-UEN A
Section 15
Metering
529
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...