16.5.3
Settings
Table 451:
GOOSEVCTRCONF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SendOperation
Off
On
-
-
On
Send operation
SendInterval
0.1 - 5.0
s
0.1
0.3
Send interval
ReceiveOperation
Off
On
-
-
On
Receive operation
ReceiveInterval
0.1 - 10.0
s
0.1
0.8
Receive interval
16.6
GOOSE voltage control receiving block
GOOSEVCTRRCV
16.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE voltage control receiving block
GOOSEVCTRR
CV
-
-
16.6.2
Functionality
GOOSEVCTRRCV component receives the voltage control data from GOOSE
network at the user defined rate.
This component also checks the received data validity, communication validity and
test mode. Communication validity will be checked upon the rate of data reception.
Data validity also depends upon the communication. If communication is invalid then
data validity will also be invalid. IEC 61850 also checks for data validity using
internal parameters which will also be passed to the DATAVALID output.
16.6.3
Function block
IEC10000252-1-en.vsd
GOOSEVCTRRCV
BLOCK
VCTR_RCV
DATAVALID
COMMVALID
TEST
IEC10000252 V1 EN
Figure 241:
GOOSEVCTRRCV function block
Section 16
1MRK 504 135-UEN A
Station communication
542
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...