12.2.2.5
Signals
Table 201:
A1A2_BS Input signals
Name
Type
Default
Description
QA1_OP
BOOLEAN
0
QA1 is in open position
QA1_CL
BOOLEAN
0
QA1 is in closed position
QB1_OP
BOOLEAN
0
QB1 is in open position
QB1_CL
BOOLEAN
0
QB1 is in closed position
QB2_OP
BOOLEAN
0
QB2 is in open position
QB2_CL
BOOLEAN
0
QB2 is in closed position
QC3_OP
BOOLEAN
0
QC3 is in open position
QC3_CL
BOOLEAN
0
QC3 is in closed position
QC4_OP
BOOLEAN
0
QC4 is in open position
QC4_CL
BOOLEAN
0
QC4 is in closed position
S1QC1_OP
BOOLEAN
0
QC1 on bus section 1 is in open position
S1QC1_CL
BOOLEAN
0
QC1 on bus section 1 is in closed position
S2QC2_OP
BOOLEAN
0
QC2 on bus section 2 is in open position
S2QC2_CL
BOOLEAN
0
QC2 on bus section 2 is in closed position
BBTR_OP
BOOLEAN
0
No busbar transfer is in progress
VP_BBTR
BOOLEAN
0
Status are valid for apparatuses involved in the
busbar transfer
Table continues on next page
Section 12
1MRK 504 135-UEN A
Control
278
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...