Name
Type
Description
I_RANGE
INTEGER
Calculated current range
F
REAL
System frequency magnitude of deadband value
F_RANGE
INTEGER
System frequency range
14.1.2.4
Settings
Table 329:
CVMMXN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
-
-
L1, L2, L3
Selection of measured current and
voltage
PowAmpFact
0.000 - 6.000
-
0.001
1.000
Amplitude factor to scale power
calculations
PowAngComp
-180.0 - 180.0
Deg
0.1
0.0
Angle compensation for phase shift
between measured I & U
k
0.00 - 1.00
-
0.01
0.00
Low pass filter coefficient for power
measurement
SLowLim
0.0 - 2000.0
%SB
0.1
80.0
Low limit in % of SBase
SLowLowLim
0.0 - 2000.0
%SB
0.1
60.0
Low Low limit in % of SBase
SMin
0.0 - 2000.0
%SB
0.1
50.0
Minimum value in % of SBase
SMax
0.0 - 2000.0
%SB
0.1
200.0
Maximum value in % of SBase
SRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
PMin
-2000.0 - 2000.0
%SB
0.1
-200.0
Minimum value in % of SBase
PMax
-2000.0 - 2000.0
%SB
0.1
200.0
Maximum value in % of SBase
PRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
QMin
-2000.0 - 2000.0
%SB
0.1
-200.0
Minimum value in % of SBase
QMax
-2000.0 - 2000.0
%SB
0.1
200.0
Maximum value in % of SBase
QRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
PFMin
-1.000 - 1.000
-
0.001
-1.000
Minimum value
PFMax
-1.000 - 1.000
-
0.001
1.000
Maximum value
Table continues on next page
Section 14
1MRK 504 135-UEN A
Monitoring
412
Technical manual
Summary of Contents for ret650
Page 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Page 2: ......
Page 40: ...34 ...
Page 62: ...56 ...
Page 84: ...78 ...
Page 208: ...202 ...
Page 376: ...370 ...
Page 414: ...408 ...
Page 530: ...524 ...
Page 562: ...556 ...
Page 620: ...614 ...
Page 668: ...662 ...
Page 669: ...663 ...