Technical data
399
ACH550-01 User's Manual
400 V drives
400 V drives (IP21 and IP54) can deliver following currents
continuously (24 hours a day, 7 days a week and 365 days a
year) in different ambient temperatures. These currents are
available up to 1000 m (3300 ft).
Type
Frame
size
P
40
I
35
I
40
I
45
I
50
M2000
ACH550-01-
kW
A
A
A
A
A
02A4-4
R1
0.75 2.5
2.4
2.3
2.2
1.93
03A3-4
R1
1.1
3.4
3.3
3.1
3.0
2.65
04A1-4
R1
1.5
4.2
4.1
3.9
3.7
3.50
05A4-4
R1
2.2
5.5
5.4
5.1
4.9
4.85
06A9-4
R1
3
7.0
6.9
6.6
6.3
6.30
08A8-4
R1
4
9.0
8.8
8.6
8.3
8.29
012A-4
R1
5.5
12.1
11.9
11.4
10.9
10.90
015A-4
R2
7.5
15.7
15.4
14.9
14.4
14.40
023A-4
R2
11
23.5
23.0
22.0
20.9
20.87
031A-4
R3
15
32
31
30
28
27.97
038A-4
R3
18.5 39
38
36
34
34.12
045A-4
R3
22
46
45
43
41
39.44
059A-4
R4
30
60
59
56
53
53
072A-4
R4
37
73
72
70
67
67
087A-4
R4
45
89
87
84
80
80
125A-4
R5
55
128
125
119
113
98
157A-4
R6
75
160
157
149
141
138
180A-4
R6
90
184
180
171
162
162
195A-4
R6
110
208
205
195
185
203
246A-4
R6
132
250
246
234
221
239
290A-4
R6
160
293
290
275
261
286
00467918.xls C
P
40
:
Typical motor power at 40 °C
I
xx
:
Drive output current at xx °C
M2000: ABB M2 motor nominal current
(Catalogue BU/General purpose
motors EN 12-2005)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com