Real-time clock and timed functions
135
ACH550-01 User's Manual
Example of timer use
The following example shows how a timer is used and
connected to different parameters. The example uses the same
settings as application macro 9 Internal timer with constant
speeds. In this example, the timer will be set to function every
weekday from 6 AM to 8 AM and 4 PM to 6 PM. On weekends,
the timer is activated between 10 AM and 12 AM and 8 PM and
10 PM.
You can use the Timed Functions Assistant for easy configuring.
For more information on the assistants, see page
76
.
1.
Go to parameter
Group 36: TIMED FUNCTIONS
and
enable the timer. The timer can be enabled directly or
through any free digital input.
2.
Go to parameters 3602…3605 and set the start time to
6 AM and stop time to 8 AM. Then set the start and stop
days to Monday and Friday. Now time period 1 is set.
3.
Go to parameters 3606…3609 and set the start time to
4 PM and stop time to 6 PM. Then set the start and stop
days to Monday and Friday. Now time period 2 is set.
4.
Go to parameters 3610…3613 and set the start time to
10 AM and stop time to 12 AM. Then set the start and stop
days to Saturday and Sunday. Now time period 3 is set.
Mon
Tue
Wed
Thu
Fri
Sat
Sun
00:00
06:00
08:00
10:00
12:00
16:00
18:00
20:00
22:00
Time period 1
Time period 2
Time period 3
Time period 4