Technical data
397
ACH550-01 User's Manual
IEC ratings, 208…240 V drives
Type
Valid up to 40 °C
Frame
size
ACH550-01-
I
2N
A
P
N
kW
Max. current
I
MAX
A
Three-phase supply voltage, 208…240 V
04A6-2
4.6
0.75
6.3
R1
06A6-2
6.6
1.1
8.3
R1
07A5-2
7.5
1.5
11.9
R1
012A-2
11.8
2.2
13.5
R1
017A-2
16.7
4.0
21.2
R1
024A-2
24.2
5.5
30.1
R2
031A-2
30.8
7.5
43.6
R2
046A-2
46
11
55
R3
059A-2
59
15
83
R3
075A-2
75
18.5
107
R4
088A-2
88
22
135
R4
114A-2
114
30
158
R4
143A-2
143
37
205
R6
178A-2
178
45
270
R6
221A-2
221
55
320
R6
248A-2
248
75
346
R6
00467918.xls C
I
MAX
: Maximum output current allowed for 2 seconds every minute
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com