Parameter listing and descriptions
327
ACH550-01 User's Manual
Group 98: OPTIONS
This group configures for options, in particular, enabling serial
communication with the drive.
Code Description
Range
9802
COMM PROT SEL
0…5
Selects the communication protocol.
0 =
NOT
SEL
– No communication protocol selected.
1 =
STD
MODBUS
– The drive communicates via a Modbus controller via
the RS485 serial link (X1 communications, terminal).
• See also parameter
Group 53: EFB PROTOCOL
.
2 =
N
2 – The drive communicates via an N2 controller via the RS485
serial link (X1 communications, terminal).
• See also parameter
Group 53: EFB PROTOCOL
.
3 =
FLN
– The drive communicates via an FLN controller via the RS485
serial link (X1 communications, terminal).
• See also parameter
Group 53: EFB PROTOCOL
.
4 =
EXT
FBA
– The drive communicates via a fieldbus adapter module in
option slot 2 of the drive.
• See also parameter
Group 51: EXT COMM MODULE
.
5 =
BACNET
– The drive communicates via a BACnet controller via the
RS485 serial link (X1 communications, terminal).
• See also parameter
Group 53: EFB PROTOCOL
.