242
Parameter listing and descriptions
ACH550-01 User's Manual
Group 29: MAINTENANCE TRIG
This group defines usage levels and trigger points. When usage
reaches the set trigger point, a notice displayed on the control
panel (operator keypad) signals that maintenance is due.
Code Description
Range
2901
COOLING FAN TRIG
0.0…6553.5 kh
Sets the trigger point for the drive’s cooling fan counter.
• Value is compared to parameter 2902 value.
0.0 – Disables the trigger.
2902
COOLING FAN ACT
0.0…6553.5 kh
Defines the actual value of the drive’s cooling fan counter.
• When parameter 2901 has been set to a non-zero value, the counter
starts.
• When the actual value of the counter exceeds the value defined by
parameter 2901, a maintenance notice is displayed on the panel.
0.0 – Resets the parameter.
2903
REVOLUTION TRIG
0…65535 Mrev
Sets the trigger point for the motor’s accumulated revolutions counter.
• Value is compared to parameter 2904 value.
0 – Disables the trigger.
2904
REVOLUTION ACT
0…6553 Mrev
Defines the actual value of the motor’s accumulated revolutions
counter.
• When parameter 2903 has been set to a non-zero value, the counter
starts.
• When the actual value of the counter exceeds the value defined by
parameter 2903, a maintenance notice is displayed on the panel.
0 – Resets the parameter.
2905
RUN TIME TRIG
0.0…6553.5 kh
Sets the trigger point for the drive’s run time counter.
• Value is compared to parameter 2906 value.
0.0 – Disables the trigger.
2906
RUN TIME ACT
0.0…6553.5 kh
• When parameter 2905 has been set to a non-zero value, the counter
starts.
• When the actual value of the counter exceeds the value defined by
parameter 2905, a maintenance notice is displayed on the panel.
Defines the actual value of the drive’s run time counter.
0.0 – Resets the parameter.