146
Serial communications
ACH550-01 User's Manual
BACnet-specific communication parameters
5309
EFB STATUS
0…7
Contains the status of the EFB protocol.
0 =
IDLE
– EFB protocol is configured, but not receiving any messages.
1 =
EXECUT
INIT
– EFB protocol is initializing.
2 =
TIME
OUT
– A time-out has occurred in the communication between
the network master and the EFB protocol.
3 =
CONFIG
ERROR
– EFB protocol has a configuration error.
4 =
OFF
-
LINE
– EFB protocol is receiving messages that are NOT
addressed to this drive.
5 =
ON
-
LINE
– EFB protocol is receiving messages that are addressed to
this drive.
6 =
RESET
– EFB protocol is performing a hardware reset.
7 =
LISTEN
ONLY
– EFB protocol is in listen-only mode.
5318
EFB PAR 18
0…65535
For Modbus only: Slave response delay. Sets additional delay in
milliseconds before the drive begins transmitting response to the
master request.
5310
EFB PAR 10
0…65535
Sets the BACnet MS/TP response turn-around time, in milliseconds.
5311
EFB PAR 11
0…65535
Sets, together with parameter 5317
EFB
PAR
17, BACnet instance IDs:
•
For the range 1 to 65535: This parameter sets the ID directly (5317
must be 0). For example, the following values set the ID to 49134:
5311 = 49134 and 5317 = 0.
•
For IDs > 65535: The ID equals parameter 5311’s value plus 10000
times parameter 5317’s value. For example, the following values set
the ID to 71234: 5311 = 1234 and 5317 = 7.
5312
EFB PAR 12
0…65535
Sets the BACnet Device Object Max Info Frames property.
5313
EFB PAR 13
0…65535
Sets the BACnet Device Object Max Master property.
5316
EFB PAR 16
0…65535
Indicates the count of MS/TP tokens passed to this drive.
5317
EFB PAR 17
0…65535
Works with parameter 5311 to set BACnet instance IDs. See parameter
5311.