158
Serial communications
ACH550-01 User's Manual
1606
LOCAL LOCK
-6…8
Defines control for the use of the HAND mode. The HAND mode allows
drive control from the control panel (operator keypad).
• When
LOCAL
LOCK
is active, the control panel cannot change from
the AUTO mode to the HAND mode.
8 =
COMM
– Defines bit 14 of Command Word 1 (parameter 0301) as the
control for setting the local lock.
• The Command Word is supplied through fieldbus communication.
1607
PARAM SAVE
0=DONE, 1=SAVE
Saves all altered parameters to the permanent memory.
• Parameters altered through a fieldbus are not automatically saved to
the permanent memory. To save, you must use this parameter.
• If 1602
PARAMETER
LOCK
= 2 (
NOT
SAVED
), parameters altered from
the control panel (operator keypad) are not saved. To save, you must
use this parameter.
• If 1602
PARAMETER
LOCK
= 1 (
OPEN
), parameters altered from the
control panel are stored immediately to permanent memory.
0 =
DONE
– The value changes automatically when all parameters are
saved.
1 =
SAVE
… – Saves altered parameters to the permanent memory.
1608
START ENABLE 1
-6…7
Selects the source of the Start enable 1 signal. See the figure on page
214
.
Note:
Start enable functionality
differs
from the Run enable
functionality.
7 =
COMM
– Assigns the fieldbus Command Word as the source for the
Start enable 1 signal.
• Bit 2 of Command Word 2 (parameter 0302) activates the Start
disable 1 signal.
• See the fieldbus user’s manual for detailed instructions.
1609
START ENABLE 2
-6…7
Selects the source of the Start enable 2 signal.
Note:
Start enable functionality
differs
from the Run enable
functionality.
7 =
COMM
– Assigns the fieldbus Command Word as the source for the
Start enable 2 signal.
• Bit 3 of Command Word 2 (parameter 0302) activates the Start
disable 2 signal.
• See the fieldbus user’s manual for detailed instructions.
Code Setting for fieldbus control & description Range
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com