198
Parameter listing and descriptions
ACH550-01 User's Manual
1209
TIMED MODE SEL
1=EXT/CS1/2/3
2=CS1/2/3/4
Defines timer-activated constant speed mode. Timers can be used to
change between the external reference and constant speeds when
parameter 1201 = 15…18 (
TIMER
1…4) or 19 (
TIMER
1 & 2).
1 =
EXT
/
CS
1/2/3
• If parameter 1201 = 15…18 (
TIMER
1…4), selects an external speed
when timer 1…4 is not active and selects constant speed 1 if it is
active.
• If parameter 1201 = 19 (
TIMER
1 & 2), selects an external speed
when no timer is active, selects constant speed 1 when only timer 1
is active, selects constant speed 2 when only timer 2 is active and
selects constant speed 3 when both timers 1 and 2 are active.
2 =
CS
1/2/3/4
• If parameter 1201 = 15…18 (
TIMER
1…4), selects constant speed 1
when timer 1…4 is not active and selects constant speed 2 if it is
active.
• If parameter 1201 = 19 (
TIMER
1 & 2), selects constant speed 1
when no timer is active, selects constant speed 2 when only timer 1
is active, selects constant speed 3 when only timer 2 is active and
selects constant speed 4 when both timers 1 and 2 are active.
Code Description
Range
TIMER
1…4
Function
0
External reference
1
Constant speed 1 (1202)
TIMER
1
TIMER
2 Function
0
0
External reference
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
TIMER
1…4
Function
0
Constant speed 1 (1202)
1
Constant speed 2 (1203)
TIMER
1
TIMER
2 Function
0
0
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
0
1
Constant speed 3 (1204)
1
1
Constant speed 4 (1205)