416
Technical data
ACH550-01 User's Manual
1
Digital input impedance 1.5 kohm. Maximum voltage for digital
inputs is 30 V.
2
Default values depend on the macro used. Values specified are for
the default macro. See chapter
Application macros and wiring
.
Note:
Terminals 3, 6, and 9 are at the same potential.
Note:
For safety reasons the fault relay signals a “fault” when
the ACH550 is powered down.
10
+24V
Auxiliary voltage output 24 V DC / 250 mA (reference to
GND). Short circuit protected.
11
GND
Auxiliary voltage output common (connected internally as
floating).
12
DCOM
Digital input common. To activate a digital input, there
must be
≥+
10 V (or
≤
-10 V) between the input and
DCOM. The 24 V may be provided by the ACH550
(X1:10) or by an external 12…24 V source of either
polarity.
13
DI1
Digital input 1, programmable. Default
2
= start/stop.
14
DI2
Digital input 2, programmable. Default
2
= not used.
15
DI3
Digital input 3, programmable. Default
2
= constant
speed 1 (parameter 1202).
16
DI4
Digital input 4, programmable. Default
2
= Start enable 1
(parameter 1608).
17
DI5
Digital input 5, programmable. Default
2
= not used.
18
DI6
Digital input 6, programmable. Default
2
= not used.
19
RO1C
Relay output 1, programmable
Default
2
= Ready
Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)
20
RO1A
21
RO1B
22
RO2C
Relay output 2, programmable
Default
2
= Running
Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)
23
RO2A
24
RO2B
25
RO3C
Relay output 3, programmable
Default
2
= Fault (-1)
Maximum: 250 V AC / 30 V DC, 2 A
Minimum: 500 mW (12 V, 10 mA)
26
RO3A
27
RO3B
X1
Hardware description
D
ig
ita
l i
n
p
u
ts
1
Re
lay out
pu
ts
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com