ACH550-01 User's Manual
96
Application macros and wiring
1. HVAC default
The HVAC default application macro is used e.g. for typical BMS
applications.
The factory set configuration of inputs and outputs of the drive is
as shown in the figure on page
97
.
When using a direct speed reference in the AUTO mode, the
speed reference must be connected to analogue input 1 (AI1)
and the START command is given with digital input 1 (DI1). In
the HAND/OFF mode, the speed reference and START
command are given through the control panel (operator keypad).
If process PI(D) is used, the feedback signal must be connected
to analogue input 2 (AI2). By default, the setpoint is set from the
control panel, but it can also be changed to analogue input 1.
Process PI(D) must be commissioned and adjusted with
parameters (
Group 40: PROCESS PID SET 1
) or using the PID
control assistant (recommended).