252
Parameter listing and descriptions
ACH550-01 User's Manual
3106
AR UNDERVOLTAGE
0=DISABLE, 1=ENABLE
Sets the automatic reset for the undervoltage function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
DC
UNDERVOLT
) after the delay set by
3103
DELAY
TIME
, and the drive resumes normal operation.
3107
AR AI<MIN
0=DISABLE, 1=ENABLE
Sets the automatic reset for the analogue input less than the minimum
value function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
AI
<
MIN
) after the delay set by 3103
DELAY
TIME
, and the drive resumes normal operation.
WARNING!
When the analogue input signal is restored, the drive
may restart, even after a long stop. Make sure that automatic, long
delayed starts will not cause physical injury and/or damage
equipment.
3108
AR EXTERNAL FLT
0=DISABLE, 1=ENABLE
Sets the automatic reset for external faults function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
EXT
FAULT
1 or
EXT
FAULT
2) after the
delay set by 3103
DELAY
TIME
, and the drive resumes normal
operation.