Parameter listing and descriptions
203
ACH550-01 User's Manual
35 =
COMM
– Energise the relay based on the input from the fieldbus
communication.
• Fieldbus writes a binary code in parameter 0134 that energises
relay 1…relay 6 according to the table below.
• 0 = De-energise the relay, 1 = Energise the relay.
36 =
COMM
(-1) – Energise the relay based on the input from the fieldbus
communication.
• Fieldbus writes a binary code in parameter 0134 that energises
relay 1…relay 6 according to the table below.
• 0 = De-energise the relay, 1 = Energise the relay.
37 =
TIMER
1 – Energise the relay when timer 1 is activated.
• See
Group 36: TIMED FUNCTIONS
.
38…40 =
TIMER
2…4 – Energise the relay when timer 2…4 is active.
• See
TIMER
1 above.
41 =
MNT
TRIG
FAN
– Energise the relay when the cooling fan counter is
triggered.
42 =
MNT
TRIG
REV
– Energise the relay when the revolutions counter is
triggered.
43 =
MNT
TRIG
RUN
– Energise the relay when the run time counter is
triggered.
44 =
MNT
TRIG
MWH
– Energise the relay when the power consumption
counter is triggered.
45 =
OVERRIDE
– Energise the relay when override is activated.
46 =
START
DELAY
– Energise relay when a start delay is active.
47 =
USER
LOAD
C
– Energise the relay when a user load curve fault or
alarm occurs.
Code Description
Range
Par. 0134
Binary
RO6
RO5 RO4 RO3 RO2 RO1
0
000000
0
0
0
0
0
0
1
000001
0
0
0
0
0
1
2
000010
0
0
0
0
1
0
3
000011
0
0
0
0
1
1
4
000100
0
0
0
1
0
0
5…62
…
…
…
…
…
…
…
63
111111
1
1
1
1
1
1
Par. 0134
Binary
RO6
RO5 RO4 RO3 RO2 RO1
0
000000
1
1
1
1
1
1
1
000001
1
1
1
1
1
0
2
000010
1
1
1
1
0
1
3
000011
1
1
1
1
0
0
4
000100
1
1
1
0
1
1
5…62
…
…
…
…
…
…
…
63
111111
0
0
0
0
0
0