Parameter listing and descriptions
309
ACH550-01 User's Manual
8113
LOW FREQ 2
0.0…500 Hz
Sets the frequency limit used to stop the second auxiliary motor.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
The second auxiliary motor stops if:
• two auxiliary motors are running.
• ACH550 output frequency drops below the limit 8113 - 1.
• output frequency stays below the relaxed limit (8113 + 1 Hz) for at
least the time 8116
AUX
MOT
STOP
D
.
8114
LOW FREQ 3
0.0…500 Hz
Sets the frequency limit used to stop the third auxiliary motor.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
The third auxiliary motor stops if:
• three auxiliary motors are running.
• ACH550 output frequency drops below the limit: 8114 - 1.
• output frequency stays below the relaxed limit (8114 + 1 Hz) for at
least the time 8116
AUX
MOT
STOP
D
.
8115
AUX MOT START D
0.0…3600 s
Sets the Start Delay for the auxiliary motors.
• The output frequency must remain above the start frequency limit
(parameter 8109, 8110 or 8111) for this time period before the
auxiliary motor starts.
• See 8109
START
FREQ
1 for a complete description of the operation.
8116
AUX MOT STOP D
0.0…3600 s
Sets the Stop Delay for the auxiliary motors.
• The output frequency must remain below the low frequency limit
(parameter 8112, 8113 or 8114) for this time period before the
auxiliary motor stops.
• See 8112
LOW
FREQ
1 for a complete description of the operation.